Dell UPS Management Software: Activating redundancy and virtualization modules
6
The fix: Enabling the Shutdown module
To properly configure the Dell MUMC software to eliminate this erroneous error message:
When the Virtualization and Redundancy modules are activated, the Shutdown module needs to be
activated in the Module Settings as well. The following procedure shows how to successfully activate
the Shutdown module and eliminate these unnecessary error messages.
1. Log into the MUMC software, and go the “Settings” menu.
Figure 4. MUMC Settings System logs
2. Click “System” under the “Settings” menu to navigate to the System page.
Figure 5. MUMC Settings System information