Force10 Node Manager Guide, version 1.5 117
Overview
Force10 Node Manager uses simulations of LEDs to indicate major and minor alarms for these conditions:
fan tray status
power supply status
•RPM status
high temperature on RPMs
line card status
high temperature on line cards
SFM status
high temperature on SFMs
A major alarm is any fault that would render the chassis non-functional.
A minor alarm is any fault that threatens the operation of the chassis.
You also can configure audible alarms on the chassis itself and configure the chassis to send an SNMP
trap. For more information about these features, please see the FTOS Command Line Interface
Reference.
Alarm Logging and Multiple Alarm Occurrences
The E-Series logs alarms for each occurrence, but it may not send an event log for multiple occurrences.
For example, whenever a module exceeds the shutdown threshold, the module shuts down. If more than
one module exceeds the warning or high temperature thresholds within a five-minute period, the system
generates one event for all effected modules, but logs alarms for each occurrence. If the modules
temperature falls to 5° lower than the warning threshold temperature, the system clears the alarm and an
SNMP trap.
Appendix B Alarms