Configuring Power Center 128
When are the settings effective?
Immediately.
Protocol Type Device Timeout Settings
These settings are used to configure the timeout between devices and the
Power Center server.
•IPMI
—
Communication timeout between Power Center and an IPMI-
enabled device (1-20 seconds). The default is 3 seconds.
•SNMP
—
Communication timeout between Power Center and a SNMP-
enabled device (1-20 seconds). The default is 3 seconds.
•WS-MAN
—
Communication timeout between Power Center and a WS-
MAN device (5-180 seconds). The default is 60 seconds.
When are the settings effective?
From the next time Power Center tries to communicate with the affected
device.
Energy Consumption Settings
These settings are used to calculate the energy consumption cost.
•Flat Rate
—
The rate of the power per kilowatt-hour (kWh); it uses the
currency you set in Default Units. The default is 0.
• Cooling Multiplier
—
The multiplier enables estimating the energy
needed to cool the device/group. The default is 1.5. For more information
on how the cooling multiplier is applied, see "Viewing Energy
Consumption" in the "Power Monitoring" chapter.
When are the settings effective?
• Flat Rate
—
From beginning of the next hour. For example, if you changed
the setting on 8:15, the new setting will be effective from 9:00.
• Cooling Multiplier
—
Immediately.
SNMP Traps Settings
These settings are used to enable Power Center to send the following custom
events to your preferred third-party applications: